2 The Port field is used to indicate the port on the
Intelligent Controller where this output module is
located. The default Port is 6, but it can be set to
3, 4, or 5 as well.
3 Use the Number of Errors before Going Off-
Line field to indicate the number of tries the
panel should make to "talk" to the communica-
tion server [without receiving an understandable
answer] before tripping the offline trigger. This
field defaults to 3.
4 Select the Enable Communication with SIO
check box only when the board is installed [not
before]. The default for this box is selected.
Programming